Skip to content
BEST ONE KO
FFU ULPA / HEPA Filter

FFU ULPA / HEPA Filter

The element that goes inside a fan filter unit. Choose ULPA at 99.99995% on 0.1㎛ or HEPA at 99.97% on 0.3㎛; initial pressure drop stays under 9.5mmAq at 0.35m/s, so the fan works less. Drops straight into ceiling units for Class 1–10 cleanrooms.

Efficiency 99.99995% @0.1㎛ / 99.97% @0.3㎛

Used in

  • FFU (Fan Filter Unit)
  • Cleanroom (Class 1–10)
  • Semiconductor / Display

Construction

Media
Glass Fiber
Gasket
Neoprene Sponge
Frame
Aluminum
Sealant
Polyurethane
Separator
AL, Kraft Paper, Hot Melt

Specifications

← swipe to scroll

Model Size H×W×D (mm) Efficiency Air flow (CMM) Initial pressure drop (mmAq) Final pressure drop (mmAq)
BO-FU515 572×1172×50 99.99995%↑ (0.1㎛) 15 9.5 19
BO-FU517 572×1172×75 99.99995%↑ (0.1㎛) 15 9.5 19
BO-FU5112 572×1172×120 99.99995%↑ (0.1㎛) 15 9.5 19
BO-FH515 572×1172×50 99.97%↑ (0.3㎛) 15 9.5 19
BO-FH517 572×1172×75 99.97%↑ (0.3㎛) 15 9.5 19
BO-FH5112 572×1172×120 99.97%↑ (0.3㎛) 15 9.5 19

Custom sizes available on request.